Work completed in Bowdon, GA!
- Merlin Fueling

- Jan 13
- 1 min read
When water decides to take a swim where it doesn't belong, our team is ready to dive in and sort things out! We recently tackled a situation involving a couple of tanks that had more liquid than planned. Tank 2 RUL was reporting a 2-inch water level, and Tank 5 diesel was showing 1 inch on the ATG. Our pros went straight to work, pulling probes and fine-tuning heights to ensure the Automatic Tank Gauge (ATG) was singing the right tune. After a good 'sticking' of the tanks, we confirmed the watery situation in RUL and found that Tank 5 diesel was nearly dry, pointing towards some debris as the culprit. The main issue? A damaged RUL probe cap, missing a crucial ear, was letting the water party crash the system. We've recommended a thorough water and debris removal for both tanks and a fresh, properly sealed RUL probe cap to keep things flowing correctly. Ready to give your tanks a spa day and send unwanted water packing? Give us a buzz or shoot a text to 470-309-7202, and let's schedule your service!